How to Brief Jointing Tech for a Package Substation
Step 1: Capture your electrical requirements
Start with the essentials of your electrical demand:
- Current load requirement in kVA.
- Expected future growth in demand.
- Supply voltage and fault level information.
- Type of supply required, such as a new connection, network upgrade or additional site capacity.
- Expected load profile, including any high-demand equipment or operational peaks.
This information helps us recommend a suitable transformer rating and configuration. Jointing Tech can supply package substations with transformer ratings from 315kVA to 1500kVA, helping suit a range of commercial, industrial, infrastructure and renewable-energy projects.
Consider both immediate and future requirements. For example, planned EV charging, new machinery, expansion phases or additional buildings can materially change the transformer capacity needed.
If you are unsure about the information available, use our Ask the Expert service for technical guidance before finalising your brief.
Step 2: Gather DNO or IDNO information
Gather any documents and information provided by your DNO/IDNO. These requirements are significant because they may directly affect the equipment and configuration needed for the connection.
Your brief should include:
- Existing or proposed connection agreements.
- G81 documents or other relevant technical specifications.
- Network drawings, where available.
- Any required protection, metering or switching arrangements.
- Specific equipment preferences, approvals or constraints.
- The relevant DNO or IDNO area.
Jointing Tech designs package substations to meet applicable DNO and IDNO requirements, using DNO-compatible RMUs and G81-approved solutions. Providing these documents at the beginning helps avoid specification changes, approval delays and redesign work later in the project.
If your scheme is being delivered through an ICP, visit our Independent Connection Providers page to find out how Jointing Tech supports ICP projects.
Step 3: Define site constraints
A suitable technical design also needs to work in the real conditions of your site. Before requesting a quotation, consider the practical details that can affect the housing, base, delivery and installation.
Include the following in your brief:
- Available footprint for the substation.
- Site drawings, layouts or photographs, where available.
- Access for delivery vehicles and lifting equipment.
- Delivery route restrictions, gates, turning areas and ground conditions.
- Environmental conditions, such as coastal, industrial or urban locations.
- Security requirements.
- Planning, visual or aesthetic considerations.
- Any restrictions on working hours or installation dates.
These factors influence whether a GRP housing or brick-built enclosure is most suitable, as well as the base, ventilation and grating options required.
Step 4: Choose core components
Based on your load, network and site requirements, start considering the core elements of the package substation:
- Transformer rating, including 315kVA, 500kVA, 800kVA, 1000kVA or 1500kVA.
- Single-ratio or dual-ratio transformer requirements.
- RMU options and any DNO-specific requirements.
- LV cabinet rating, including 800A or 1600A options.
- Number of LV outgoing ways, typically from 4-way to 7-way.
- Whether air circuit breakers, known as ACBs, are required.
- Metering, protection and future expansion needs.
The RMU provides medium-voltage switching and protection, while the LV cabinet distributes power to your site’s outgoing circuits. Ensuring these are correctly specified is essential for approval, installation and future operational flexibility.
If you do not know which configuration is right, provide the available load, site and connection information. Our team can help turn this into a suitable technical specification.
Step 5: Decide on housing, bases and accessories
The substation housing and supporting infrastructure should be included in the original brief, not treated as an afterthought.
Think about:
- Preferred GRP housing model, including TR1, TR7 or TR18.
- Ventilation requirements, including whether extra ventilation is needed.
- Pre-cast concrete bases for rapid, robust installation.
- GRP grating for safe, corrosion-resistant access.
- GRP doors and vents for brick-built enclosures.
- Generator entry-point requirements where relevant.
- Any site-specific access or security requirements.
GRP housings can support fast installation and reduce the amount of site construction required. For brick-built substations, Jointing Tech can supply GRP doors and ventilation options to support a practical, durable installation.
Step 6: Plan delivery and installation logistics
A good delivery plan ensures the project continues to progress and keeps things running smoothly on the day of installation.
Your brief should cover:
- Target delivery date and preferred installation window.
- Whether the site is ready to receive the substation.
- Vehicle access and offloading constraints.
- Final position of the substation on site.
- Any lifting, access or ground-condition limitations.
- Whether you need cables and specialist power accessories delivered with the substation.
- Storage requirements if delivery needs to be phased.
Jointing Tech includes HIAB offloading in the price and can coordinate combined deliveries of the substation, cables and accessories. This can reduce site visits, simplify procurement and help ensure critical materials arrive together.
For urgent programmes, explore substations in stock to check whether a suitable stock-led solution may be available for faster dispatch.
Final checklist
Before contacting our package substation team, try to have the following information available:
- Electrical load and fault-level information.
- Current and anticipated future demand.
- DNO or IDNO requirements and connection details.
- Site layout, constraints and environmental considerations.
- Initial thoughts on transformer rating, RMU and LV cabinet configuration.
- Housing, base, ventilation and grating preferences.
- Delivery date, access details and any combined-delivery needs.
- Supporting drawings, photographs or documents where available.
Need help preparing your brief?
Send the available information to Jointing Tech’s package substation experts, and we will turn it into a fully engineered, G81-approved solution. From transformer and RMU selection to LV cabinets, housings, bases, accessories and delivery, we can help specify, assemble and deliver a package substation ready for installation.